Two markings, one space apart in the alphabet, and a completely unrelated meaning. Class 2 is a North American limit on how much energy a circuit is allowed to deliver. Class II is an insulation classification used in IEC standards, meaning the product is protected by double or reinforced insulation and has no protective earth connection.
They are not interchangeable, they do not imply each other, and confusing them is one of the most common reasons a signage or kiosk installation fails inspection after the ceiling is closed. A driver can be Class II and not Class 2. It can also be Class 2 and not Class II. In the 24 V LED world, the majority of drivers above 100 W are Class II and not Class 2 — which surprises people who bought them because the box said “class 2” somewhere on the packaging.
This article separates the two, gives you the number that actually constrains designs, and explains why a 24 V supply effectively tops out at about 100 W if you want Class 2 wiring.
What Class 2 actually limits
NEC Article 725 defines Class 2 circuits as limited-energy circuits, and the definition is quantitative: a Class 2 circuit is one supplied by a listed Class 2 power source, with an output limited to 100 VA and 60 V. Class 3 goes up to 150 V but is still limited in power and requires different wiring methods.
The point of the limit is not electrical performance. It is fire and shock safety: below those thresholds, the code permits wiring methods that would otherwise be forbidden — CL2-rated cable instead of conduit, cable in a plenum without metal raceway, connections without a junction box in some cases, and installation by people who are not electricians in some jurisdictions.
That is the commercial value of Class 2. It is not a quality badge; it is a permission slip for cheaper wiring.
Now do the arithmetic that catches people:
| Output voltage | Maximum current for 100 VA | Practical continuous rating |
| 12 V | 8.3 A | 8 A |
| 24 V | 4.16 A | 4 A |
| 36 V | 2.7 A | 2.7 A |
| 48 V | 2.08 A | 2 A |
At 24 V, Class 2 means about 100 W, and in practice 96 W once you leave margin. That is the real ceiling, and it is far below what most signage projects want from a single driver.
A 24 V 150 W driver — a completely standard product, ours included — is 150 VA. It is over the Class 2 limit by 50%. If the project was designed around CL2 cable in a ceiling void, that driver cannot legally feed that circuit, and the fix is not a label. It is either a bigger cable in conduit, or splitting the load across multiple Class 2 supplies.
What Class II actually means
IEC Class II is about insulation, not energy.
- Class I products are earthed: the accessible metalwork is connected to protective earth, and a fault is cleared by the earth path.
- Class II products have double or reinforced insulation, no protective earth, and rely on the insulation alone. The symbol is a square inside a square.
- Class III products operate on SELV and rely on the low voltage rather than insulation.
A plastic-cased 24 V driver with a two-core input and no earth terminal is Class II. A metal-cased driver with an earth stud is Class I. The classification determines the creepage and clearance distances, the dielectric withstand test voltage, and whether the enclosure has to be earthed — not how much power it can deliver.
So a 24 V 400 W driver in an IP67 plastic case is Class II and not Class 2. It has double insulation and no earth, and it delivers 400 VA, four times the Class 2 ceiling. Both statements are true at once, and they describe different properties.
Conversely, a small 12 V 1 A wall adapter is both Class II (double insulated plastic case) and Class 2 (12 VA, under the limit). That overlap is why the confusion started: for small adapters, the two usually travel together, so people assume they are the same thing. Once you get above 100 W, they separate.
Why the label on the box is ambiguous
In the US, a Class 2 power supply must be listed to UL 1310 (Class 2 power units). A general-purpose power supply is listed to UL 1012. LED drivers are covered by UL 8750, which can be combined with UL 1310 for a Class 2 output.
So a driver’s label might carry “UL 8750” and “Class 2” together, or “UL 8750” alone, or “UL 1012”. The word “Class” appears in the listing standard numbers as well, which does not help.
The reliable way to read it: look for the Class 2 designation in the listing mark and the output rating on the same label. If the output is 24 V at 8 A (192 VA), no amount of Class 2 wording makes it a Class 2 source — the physics contradicts the label, and the inspector will read the rating, not the marketing.
Second reliable check: the installation instructions. A genuine Class 2 supply’s instructions will state the wiring methods permitted. A supply that is not Class 2 will either say nothing or explicitly require wiring per Class 1 methods.
The inspection that fails
Here is the scenario, which we see several times a year.
A signage contractor designs a double-sided pylon sign with six LED modules, total 120 W at 24 V. He specifies CL2 cable because it is cheaper, faster and does not need conduit. He orders a 24 V 150 W driver because 120 W plus 25% margin is 150 W, which is correct engineering.
The installation is neat. The inspector arrives, reads the driver label, sees 150 VA against a Class 2 limit of 100 VA, and fails the circuit. The remedy is either to replace the driver with two 75 W Class 2 units (and rewire the sign into two circuits), or to re-pull the cable in conduit with Class 1 wiring methods.
The re-pull is the expensive one, and it happens after the sign is on the pole.
The design rule that prevents this: for any circuit using CL2 cable, the total connected load must be under 100 VA and the supply must be listed as Class 2. If the load is above that, design two circuits from the start. On a pylon sign, two 60 W Class 2 drivers on two separate CL2 runs costs about €40 more than one 150 W driver, and it eliminates the entire risk.
Where SELV fits, and why it is not the same again
A third term that gets mixed in: SELV.
SELV (safety extra-low voltage) is defined in IEC 61140 and limits the voltage to 60 V DC ripple-free, or 42.4 V peak, under normal and single-fault conditions. A 24 V driver output is SELV if the isolation between mains and output meets the reinforced insulation requirement and the output is limited accordingly.
SELV is about voltage; Class 2 is about energy (voltage and power); Class II is about insulation. A 24 V 400 W driver can be SELV and Class II and not Class 2, all at once. That combination is legal, common, and completely fine — as long as the wiring is not relying on Class 2 permissions.
The practical consequence for a specifier: SELV output lets you use unskilled labour for the low-voltage side in many jurisdictions and reduces shock risk, but it does not let you use CL2 cable in a plenum. That permission comes only from Class 2.
What to specify, in the order it matters
If you are writing a specification for a project with Class 2 wiring, these four lines cover it:
- “Power supply shall be listed to UL 1310 as a Class 2 power source, with output not exceeding 100 VA.” Naming the standard removes the ambiguity that “Class 2” alone creates.
- “Output: 24 V DC, 4.0 A maximum continuous.” Stating the current makes the VA check trivial for the inspector.
- “Insulation: Class II, double insulated, no protective earth.” If the enclosure is plastic and there is no earth terminal, this is what you want stated, separately from the Class 2 requirement.
- “Installation instructions shall state the permitted wiring methods.” This is the sentence that protects you if the product is later substituted.
And for the projects where you do not need Class 2 wiring — an indoor cabinet with conduit, a luminaire with internal wiring — say so explicitly, because a Class 2 requirement would force you into multiple smaller supplies for no benefit. This is where the confusion costs money in the other direction: designers specify “Class 2” when they mean “SELV” or “Class II”, and end up splitting a 300 W load into four drivers when one would do.
Where our range sits
Most of our catalogue is Class II, not Class 2. The 150 W, 250 W, 400 W and 600 W models are all double-insulated designs above the 100 VA limit, and they are the right product for installations with Class 1 wiring methods or for luminaire-internal use. Saying otherwise would be a labelling exercise, not an engineering one.
The 60W slim IP20 power supply is 24 V at 2.5 A — 60 VA — and sits comfortably inside the Class 2 envelope, which is why it is the model we quote for signage and kiosk work that uses CL2 cable. Above that, the honest answer is either two units on two circuits, or an OEM design with a Class 2-listed output stage if the volume justifies the listing.
If a project needs more than 100 W on a single Class 2 circuit, it does not need a better driver. It needs a different circuit design, and we will say so at the quotation stage rather than after the inspection.
The mistake in the other direction
Everything above is about under-specifying — assuming a driver is Class 2 when it is not. The reverse mistake is just as common and costs more in hardware.
A designer writes “Class 2 power supply” into a specification because they have seen the phrase and associate it with safety. The electrical contractor, wanting to comply, splits a 300 W load into four 75 W supplies on four circuits. Now the project has four drivers instead of one, four sets of input wiring, four failure points, four items to stock, and a bill of materials 35% higher than it needed to be — for a requirement that was never applicable, because the installation used conduit and Class 1 wiring methods from the start.
The test is simple: does the circuit depend on Class 2 permissions? If the cable is in conduit, or the wiring is inside a luminaire, or the installation is in a jurisdiction that does not adopt NEC Article 725 for lighting, the answer is no, and Class 2 buys you nothing. What you probably wanted was SELV output, or double insulation, or both. Those are different requirements and they are met by a single 300 W Class II driver at a third of the cost.
Ask for the three properties separately and specify only the ones the installation actually needs:
- SELV output — for shock protection on accessible low-voltage conductors.
- Class II insulation — for a plastic enclosure with no earth connection.
- Class 2 listing — only when the wiring method depends on it.
Most LED installations need the first two. A minority need the third, and those are the ones where the 100 VA ceiling is a real design constraint rather than an inherited habit.
FAQ
Is a 24 V 150 W driver Class 2? No. 150 W at 24 V is 150 VA, above the 100 VA Class 2 ceiling. It may well be Class II (double insulated), which is a different classification entirely.
Can I use CL2 cable with a Class II driver? Only if the driver is also listed as a Class 2 power source. The permission to use CL2 cable comes from the Class 2 circuit definition in NEC Article 725, not from the insulation class.
What is the maximum wattage for a Class 2 LED driver at 24 V? About 96 W in practice — 24 V at 4 A. The theoretical ceiling is 100 VA, but no designer should run a supply at its limit on a circuit whose legality depends on staying under it.
Does Class II mean double insulated? Yes. Class II means protection by double or reinforced insulation with no protective earth. The symbol is a square inside a square. It says nothing about output power.
Is SELV the same as Class 2? No. SELV limits voltage; Class 2 limits voltage and power. A 400 W 24 V driver can be SELV and not Class 2. For CL2 wiring you need Class 2 specifically.
What about Canada? Canadian requirements follow CSA C22.2 No. 223 for power supplies and No. 250.13 for LED equipment, with the Class 2 concept aligned to the NEC but the listing marks different. Check for the cUL or CSA mark alongside the UL one.
Designing a signage or kiosk circuit that has to stay under 100 VA? The 60W slim IP20 power supply is 24 V at 2.5 A and listed inside the Class 2 envelope, and our OEM LED driver manufacturing line builds Class 2-listed output stages where the volume supports a dedicated listing. Send the total load and the wiring method and we will tell you how many circuits you actually need — before the cable goes in.